Lucene search

K
icsIndustrial Control Systems Cyber Emergency Response TeamICSA-17-131-02
HistoryMay 11, 2017 - 12:00 p.m.

Satel Iberia SenNet Data Logger and Electricity Meters

2017-05-1112:00:00
Industrial Control Systems Cyber Emergency Response Team
www.cisa.gov
26

9 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

SINGLE

Confidentiality Impact

COMPLETE

Integrity Impact

COMPLETE

Availability Impact

COMPLETE

AV:N/AC:L/Au:S/C:C/I:C/A:C

8.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

LOW

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

0.003 Low

EPSS

Percentile

65.5%

CVSS v3 8.8

**ATTENTION:**Remotely exploitable/low skill level to exploit

Vendor: Satel Iberia

Equipment: SenNet Data Logger and Electricity Meters

Vulnerability: Command Injection

AFFECTED PRODUCTS

The following versions of SenNet Data Logger and Electricity Meters, monitoring platforms, are affected:

  • SenNet Optimal DataLogger V5.37c-1.43c and prior,
  • SenNet Solar Datalogger V5.03-1.56a and prior, and
  • SenNet Multitask Meter V5.21a-1.18b and prior.

IMPACT

Successful exploitation of this vulnerability could allow the attacker to gain root privilege to run arbitrary commands and change system data.

MITIGATION

Satel Iberia recommends that affected users upgrade to the latest version available. The latest version can be obtained from Satel Iberia support at [email protected].

NCCIC/ICS-CERT recommends that users take defensive measures to minimize the risk of exploitation of this vulnerability. Specifically, users should:

  • Minimize network exposure for all control system devices and/or systems, and ensure that they are not accessible from the Internet.
  • Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
  • When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.

ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

ICS-CERT also provides a section for control systems security recommended practices on the ICS-CERT web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

Additional mitigation guidance and recommended practices are publicly available in the ICS‑CERT Technical Information Paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies, that is available for download from the ICS-CERT web site.

Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.

No known public exploits specifically target this vulnerability.

VULNERABILITY OVERVIEW

COMMAND INJECTION CWE-77

Successful exploitation of this vulnerability could result in the attacker breaking out of the jailed shell and gaining full access to the system.

CVE-2017-6048 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

RESEARCHER

Karn Ganeshan discovered this vulnerability.

BACKGROUND

Critical Infrastructure Sectors: Critical Manufacturing, Energy, Transportation Systems

Countries/Areas Deployed: Americas and Europe

Company Headquarters Location: Spain

References

9 High

CVSS2

Attack Vector

NETWORK

Attack Complexity

LOW

Authentication

SINGLE

Confidentiality Impact

COMPLETE

Integrity Impact

COMPLETE

Availability Impact

COMPLETE

AV:N/AC:L/Au:S/C:C/I:C/A:C

8.8 High

CVSS3

Attack Vector

NETWORK

Attack Complexity

LOW

Privileges Required

LOW

User Interaction

NONE

Scope

UNCHANGED

Confidentiality Impact

HIGH

Integrity Impact

HIGH

Availability Impact

HIGH

CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H

0.003 Low

EPSS

Percentile

65.5%

Related for ICSA-17-131-02