10 High
CVSS2
Attack Vector
NETWORK
Attack Complexity
LOW
Authentication
NONE
Confidentiality Impact
COMPLETE
Integrity Impact
COMPLETE
Availability Impact
COMPLETE
AV:N/AC:L/Au:N/C:C/I:C/A:C
0.031 Low
EPSS
Percentile
91.0%
Independent researchers Carlos Mario Penagos Hollman and Dillon Beresford identified multiple vulnerabilities in WellinTech’s KingView and a single vulnerability in WellinTech’s KingHistorian application. These vulnerabilities are exploitable remotely. WellinTech has created a patch and the researchers have validated that the patch resolves these vulnerabilities in the KingView and KingHistorian applications.
The following products and versions are affected:
Successful exploitation of these vulnerabilities could lead to arbitrary code execution, information disclosure, and denial of service (DoS).
Impact to individual organizations depends on many factors that are unique to each organization. ICS-CERT recommends that organizations evaluate the impact of this vulnerability based on their operational environment, architecture, and product implementation.
WellinTech is a software development company specializing in automation and control. WellinTech is based in Beijing, China, with branches in the United States, Japan, Singapore, Europe, and Taiwan.
According to the WellinTech Web site, the KingView product is a Windows-based control, monitoring, and data collection application deployed across several industries, including power, water, building automation, mining, and other sectors. The KingHistorian product is a database that can be used as a stand-alone historian; it is deployed across several industries including water and power and other sectors.
By sending a specially crafted packet to Port 555/TCP, an attacker may create a stack-based buffer overflow in the KingView application. This attack may allow the execution of arbitrary code.
CVE-2012-1830NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-1830, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 10 has been assigned; the CVSS vector string is AV:N/AC:L/Au:N/C:C/I:C/A:C.CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:C/I:C/A:C, Web site last visited July 3, 2012.
By sending a specially crafted packet to Port 555/TCP, an attacker may create a heap-based buffer overflow in the KingView application. This attack may allow the execution of arbitrary code.
CVE-2012-1831NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-1831, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 10 has been assigned; the CVSS vector string is AV:N/AC:L/Au:N/C:C/I:C/A:C.CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:C/I:C/A:C, Web site last visited July 3, 2012.
By sending a specially crafted packet to either Port 2001/TCP or Port 2001/UDP, an attacker may read from an invalid memory location in the KingView application. This attack may allow the execution of arbitrary code.
CVE-2012-1832NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-1832, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 10 has been assigned; the CVSS vector string is AV:N/AC:L/Au:N/C:C/I:C/A:C.CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:C/I:C/A:C, Web site last visited July 3, 2012.
By sending a specially crafted GET request via HTTP on Port 8001/TCP, an attacker may access arbitrary information from the KingView application.
CVE-2012-2560NVD, http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-2560, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 5 has been assigned. The CVSS vector string is AV:N/AC:L/Au:N/C:P/I:N/A:N.http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:P/I:N/A:N. Web site last visited July 3, 2012.
By sending a specially crafted packet to Port 5678/TCP, an attacker may create an invalid pointer write in the KingHistorian application. This attack may allow the execution of arbitrary code.
CVE-2012-2559NVD, 2560http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2012-2559, NIST uses this advisory to create the CVE Web site report. This Web site will be active sometime after publication of this advisory. has been assigned to this vulnerability. A CVSS v2 base score of 10 has been assigned; the CVSS vector string is AV:N/AC:L/Au:N/C:C/I:C/A:C.CVSS Calculator, http://nvd.nist.gov/cvss.cfm?version=2&vector=AV:N/AC:L/Au:N/C:C/I:C/A:C, Web site last visited July 3, 2012.
These vulnerabilities are exploitable remotely.
No known public exploits specifically target these vulnerabilities.
An attacker requires a moderate skill level to exploit these vulnerabilities.
WellinTech has developed patches to resolve these issues. The WellinTech advisory and the KingView product patch can be found here: <http://www.wellintech.com/index.php/news/33-patch-for-kingview653>. The WellinTech advisory and the KingHistorian product patch can be found here: <http://en2.wellintech.com/products/detail.aspx?contentid=25>.
ICS-CERT encourages asset owners to take additional defensive measures to protect against this and other cybersecurity risks.
The Control Systems Security Program (CSSP) also provides a section for control systems security recommended practices on the CSSP Web page. Several recommended practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.CSSP Recommended Practices, https://ics-cert.us-cert.gov/Recommended-Practices, Web site last accessed July 3, 2012. ICS-CERT reminds organizations to perform proper impact analysis and risk assessment prior to taking defensive measures.
Organizations observing any suspected malicious activity should follow their established internal procedures and report their findings to ICS-CERT for tracking and correlation against other incidents.
en2.wellintech.com/products/detail.aspx?contentid=25
www.wellintech.com/index.php/news/33-patch-for-kingview653
public.govdelivery.com/accounts/USDHSCISA/subscriber/new?topic_id=USDHSCISA_138
twitter.com/CISAgov
twitter.com/intent/tweet?text=WellinTech%20KingView%20Multiple%20Vulnerabilities+https://www.cisa.gov/news-events/ics-advisories/icsa-12-185-01
www.dhs.gov
www.dhs.gov/foia
www.dhs.gov/performance-financial-reports
www.facebook.com/CISA
www.facebook.com/sharer/sharer.php?u=https://www.cisa.gov/news-events/ics-advisories/icsa-12-185-01&title=WellinTech%20KingView%20Multiple%20Vulnerabilities
www.instagram.com/cisagov
www.linkedin.com/company/cybersecurity-and-infrastructure-security-agency
www.linkedin.com/sharing/share-offsite/?url=https://www.cisa.gov/news-events/ics-advisories/icsa-12-185-01
www.oig.dhs.gov/
www.surveymonkey.com/r/CISA-cyber-survey?product=https://www.cisa.gov/news-events/ics-advisories/icsa-12-185-01
www.usa.gov/
www.whitehouse.gov/
www.youtube.com/@cisagov
mailto:?subject=WellinTech%20KingView%20Multiple%20Vulnerabilities&body=www.cisa.gov/news-events/ics-advisories/icsa-12-185-01