A vulnerability has been identified in APOGEE MBC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE MEC (PPC) (P2 Ethernet) (All versions >= V2.6.3), APOGEE PXC Compact (BACnet) (All versions < V3.5.3), APOGEE PXC Compact (P2 Ethernet) (All versions >= V2.8), APOGEE PXC Modular (BACnet) (All versions < V3.5.3), APOGEE PXC Modular (P2 Ethernet) (All versions >= V2.8), TALON TC Compact (BACnet) (All versions < V3.5.3), TALON TC Modular (BACnet) (All versions < V3.5.3). The web server of affected devices lacks proper bounds checking when parsing the Host parameter in HTTP requests, which could lead to a buffer overflow. An unauthenticated remote attacker could exploit this vulnerability to execute arbitrary code on the device with root privileges.
[
{
"product": "APOGEE MBC (PPC) (P2 Ethernet)",
"vendor": "Siemens",
"versions": [
{
"status": "affected",
"version": "All versions >= V2.6.3"
}
]
},
{
"product": "APOGEE MEC (PPC) (P2 Ethernet)",
"vendor": "Siemens",
"versions": [
{
"status": "affected",
"version": "All versions >= V2.6.3"
}
]
},
{
"product": "APOGEE PXC Compact (BACnet)",
"vendor": "Siemens",
"versions": [
{
"status": "affected",
"version": "All versions < V3.5.3"
}
]
},
{
"product": "APOGEE PXC Compact (P2 Ethernet)",
"vendor": "Siemens",
"versions": [
{
"status": "affected",
"version": "All versions >= V2.8"
}
]
},
{
"product": "APOGEE PXC Modular (BACnet)",
"vendor": "Siemens",
"versions": [
{
"status": "affected",
"version": "All versions < V3.5.3"
}
]
},
{
"product": "APOGEE PXC Modular (P2 Ethernet)",
"vendor": "Siemens",
"versions": [
{
"status": "affected",
"version": "All versions >= V2.8"
}
]
},
{
"product": "TALON TC Compact (BACnet)",
"vendor": "Siemens",
"versions": [
{
"status": "affected",
"version": "All versions < V3.5.3"
}
]
},
{
"product": "TALON TC Modular (BACnet)",
"vendor": "Siemens",
"versions": [
{
"status": "affected",
"version": "All versions < V3.5.3"
}
]
}
]