A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known.
[
{
"product": "SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants)",
"vendor": "Siemens AG",
"versions": [
{
"status": "affected",
"version": "All versions < V3.X.17"
}
]
},
{
"product": "SIMATIC TDC CP51M1",
"vendor": "Siemens AG",
"versions": [
{
"status": "affected",
"version": "All versions < V1.1.8"
}
]
},
{
"product": "SIMATIC TDC CPU555",
"vendor": "Siemens AG",
"versions": [
{
"status": "affected",
"version": "All versions < V1.1.1"
}
]
},
{
"product": "SINUMERIK 840D sl",
"vendor": "Siemens AG",
"versions": [
{
"status": "affected",
"version": "All versions < V4.8.6"
}
]
},
{
"product": "SINUMERIK 840D sl",
"vendor": "Siemens AG",
"versions": [
{
"status": "affected",
"version": "All versions < V4.94"
}
]
}
]